Device object – Yaskawa BACnet MS/TP User Manual

Page 39

Advertising
background image

Object ID

Object Name

Modbus

Address

Active Text

Inactive

Text

PV Access

BV47

Modbus Comms Error

002CH:bit 14

ON

OFF

R

BV48

Modbus Timeout Error

002CH:bit 15

ON

OFF

R

BV49

CRC Error

003DH:bit 0

ON

OFF

R

BV50

Invalid Data Length

003DH:bit 1

ON

OFF

R

BV51

Parity Error

003DH:bit 3

ON

OFF

R

BV52

Overrun Error

003DH:bit 4

ON

OFF

R

BV53

Framing Error

003DH:bit 5

ON

OFF

R

BV54

Timeout Error

003DH:bit 6

ON

OFF

R

BV55

<1>

Parameter Accept

0910H:bit 0

ON

OFF

W

BV56

<1>

Parameter Enter

0900H:bit 0

ON

OFF

W

BV57

Drive Comms Error

-

ON

OFF

R

<1>

Refer to Accessing Drive Parameters and the Enter Command on page 40

for an explanation of how to read

and write drive parameters not listed in the analog or binary objects.

u

Device Object

The Device Object fully describes the BACnet device to the network. Notable is that the

Device Object Instance ID and the Device Object Name are configurable.
The Device Object Instance ID is a unique internetwork-wide numerical value. It is a 22-bit

value that can range from 0 to 4,194,303. It is configurable by parameters F6-48 and F6-49.

Any changes to these parameters will not take effect until the power is cycled to the drive.
The Device Object Name is a unique internetwork-wide character string. It is a 20-character

string. It is writable from the BACnet network. Any new string written will not take effect

until the power is cycled to the drive.

10 BACnet Objects Supported

YASKAWA TOEP YEACOM 08A A1000 Option BACnet MS/TP SI-B3 Installation & Technical Manual

39