Pid for trim control – Yaskawa S12051 for GPD 515/G5 User Manual

Page 2

Advertising
background image

Flash Software-PID for Trim Control

Option S12051 for GPD 515/G5

Yaskawa Electric America, Inc-www.drives.com

02Y00025-0428 Page 2 of 11

Date: 08/23/01

PID For Trim Control

This section replaces section 5.36

(2)

The Proportional, Integral and Derivative control function provides closed-loop control, or regulation of a system process
variable (dancer position, pressure, temperature, etc.). This regulation is accomplished by comparing a feedback signal
to a setpoint reference, which results in an error signal. The PID control algorithm then performs calculations, based upon
the PID parameter settings (b5-01 thru b5-12), on this error signal. The result of the PID algorithm is then used as the
new speed reference, or to trim the existing speed reference.

5.36A. b5-01 : PID Selection



Using this parameter, PID control can be enabled, and the type of PID control can be selected.

Setting Description

0

PID Disabled

1

PID Enabled (Output Only) - PID output becomes the output frequency

2

PID Enabled (Output + Reference) - PID output “trims” the frequency reference

3

PID Enabled (Output + Reference, with accel / decel timer) - PID output “trims” the frequency reference


• If b5-01 is set to 0, no PID function will occur.

• If b5-01 is set to 1, the frequency reference the drive will use will come from the PID control only.

• If b5-01 is set to 2, the frequency reference the drive will use will be the actual frequency reference (Terminal 13 or d1-

01 thru d1-09) plus the output of the PID control. This mode could be used to perform a line speed w/dancer trim
function.

• If b5-01 is set to 3, the frequency reference the drive will use will be the actual frequency reference (Terminal 13 or

d1-01 thru d1-09) plus the output of the PID control. In addition, the accel/decel ramps will change to the settings in
C1-07 & C1-08 after the time specified in b5-08. See description of b5-08 for more details.


5.36B.
Line Speed / Frequency Reference Selection

Refer to Section 5.25 - Local/Remote and Reference Selection

(2)

in order to select the line speed. NOTE: in Section 5.25,

the “Auto” speed reference is terminal 13. The “Manual” speed reference is terminal 16, and the “Memory Data” refers to
speed reference parameters d1-01 thru d1-09.

5.36C. PID Setpoint Selection

b5-07: Position Offset


H3-05: Multi-function Analog Input 1
Selection (Term. 16)

H3-09: Multi-function Analog Input 2
Selection (Term. 14)

Select the PID control Setpoint Reference from either the internal digital setting b5-07, or from an analog input (Terminal
16 or 14). Note: if both a digital and an analog setpoint reference are used simultaneously, the two will add together.

• Voltage signal (0 -10 VDC) Terminal 16: Set H3-05 to data “20” and H3-04 to data “0”.

• Voltage signal (-10 to +10 VDC) Terminal 16: Set H3-05 to data “20” and H3-04 to data “1”.

• Current signal (4 to 20 mA) Terminal 14: Set H3-09 to data “20” and H3-08 to data “2”.

• Voltage signal

(3)

(0 -10 VDC) Terminal 14: Set H3-09 to data “20” and H3-04 to data “0”.

Voltage signal

(3)

(-10 to +10 VDC) Terminal 14: Set H3-09 to data “20” and H3-04 to data “1”.

(2)

GPD515 Technical Manual TM4515

Factory Setting: 0
Range: 0, 1, 2, 3

Factory Setting: 0.00
Range: -10.00 to +10.00V

Factory Setting: 0
Range: 0 - 21

Factory Setting: 1F
Range: 0 - 21

Advertising