Yaskawa S12051 for GPD 515/G5 User Manual

Page 5

Advertising
background image

Flash Software-PID for Trim Control

Option S12051 for GPD 515/G5

Yaskawa Electric America, Inc-www.drives.com

02Y00025-0428 Page 5 of 11

Date: 08/23/01



b5-10: PID Position High


b5-11:
PID Position Low


b5-12: PID Hysteresis


H2-01: Multi-function Output (Term. 9 & 10)
H2-02:
Multi-function Output (Term. 25-27)
H2-03: Multi-function Output (Term. 26-27)


Parameters b5-10, b5-11, and b5-12 are used in conjunction with one or two multi-function outputs. With these a Multi-
function Output can be activated when the feedback signal goes above a certain level (b5-10), or drops below a certain
level (b5-11). Parameter b5-12 determines at what point the Multi-function Output will de-energize.

Factory Setting: 10.00
Range: -10.00 - +10.00V

Factory Setting: 0.00
Range: -10.00 - +10.00V

Factory Setting: 0.10
Range: 0.00 - 1.00V

Data 40: High Position

or

Data 41: Low Position

EXAMPLE OF POSITION HIGH AND POSITION LOW OUTPUTS

Advertising