Yaskawa S12051 for GPD 515/G5 User Manual
Page 5
 
Flash Software-PID for Trim Control
Option S12051 for GPD 515/G5
Yaskawa Electric America, Inc-www.drives.com
02Y00025-0428 Page 5 of 11
Date: 08/23/01
 
 
b5-10: PID Position High 
 
 
b5-11: PID Position Low 
 
 
b5-12: PID Hysteresis 
 
 
H2-01: Multi-function Output (Term. 9 & 10) 
H2-02:  Multi-function Output (Term. 25-27) 
H2-03:  Multi-function Output (Term. 26-27)  
 
 
Parameters b5-10, b5-11, and b5-12 are used in conjunction with one or two multi-function outputs. With these a Multi-
function Output can be activated when the feedback signal goes above a certain level (b5-10), or drops below a certain 
level (b5-11). Parameter b5-12 determines at what point the Multi-function Output will de-energize. 
Factory Setting: 10.00 
Range: -10.00 - +10.00V 
Factory Setting: 0.00 
Range: -10.00 - +10.00V 
Factory Setting: 0.10 
Range: 0.00 - 1.00V 
Data 40: High Position
or
Data 41: Low Position
EXAMPLE OF POSITION HIGH AND POSITION LOW OUTPUTS