Reference units (user units) – Yaskawa MP900 User Manual

Page 13

Advertising
background image

MP920 QRG Rev1.5

Reference Units (User Units)

FP7: Rated Speed [RPM]

(Default 3000)

OLC022: Speed Reference (when

OBC001D=0

) [10^

n

RU

/min] (Default 3000)

OLC015: Speed Reference (when OBC001D=1) [0.01% of Rated Speed (FP7)] (Default 0)

OLC012: Position Reference [

RU

]

OBC001E: Incremental / Absolute

or

OLC028: Step Distance [

RU

]

OBC0212: Step Direction

OWC00C: Acceleration [ms to Rated Speed (FP7)]

(Default 0)

Servopack Pn80B: Acceleration Rate

[10,000

RU

/sec^2]

(Default 65535)

OWC00D: Deceleration [ms to Rated Speed (FP7)]

(Default 0)

Servopack Pn80E: Deceleration Rate

[10,000

RU

/sec^2]

(Default 65535)

OWC00C=0 & OWC00D =0 sets servopack acceleration/deceleration rate to 65535[10,000 RU/sec^2]

n = 3

when

FP17 bit 4 =0 (RU not used)

n = FP18 when

FP17 bit 4 =1 (RU is used)

KEY

* RU = "reference unit" = "user unit" = "command unit"

* FP = Fixed Parameter

* MCC = Motion Command Code (OWxx20)

* Register Values given for Circuit#1, Axis#/1

*

Bold type

represents default setting

RU

= FP17 bits0-3

0: Pulse (post quad)

1: mm

2: deg

3: inch

If PULSE is not chosen as the RU, use the following

parameters to define the relationship between

PULSE and RU.

FP8: Encoder Pulses (pre-quad) per motor rev

FP21: Motor Revs into gearbox

FP22: Machine Shaft Revs out of gearbox

FP19: RU per Machine Shaft Revolution

Motor

G.B.

8

21

22

19

NOTES:

* Register Addresses assume Circuit#1, Axis#1

* Reference Units not compatible with Function Block programming.

* Default Positioning units are [encoder pulses (post quad)]

* Default Speed Reference units are [1000 pulses/min]

* Default Accel/Decel units are [ms to rated motor rpm]

* MPE720 5.31B "Units" in module configuration do not update

* Motion Module Manual incorrectly lists MCC=11 and Decel (OLC00D) as

not used

Use MCC=11

to change

Deceleration

Use MCC=10

to change

A

cceleration

Use of MCC to change

Servopack Parameters

Applies to SVB ONLY and

NOT SVA

FP17 bit 4 =1 Activates RU Feature