Basic Set of Registers

for Register-Based Programming

Assume Module(Circuit) #1, Axis #1. Add 400h per circuit, 40h per axis.

Motion Setting Registers (

O

Wxxxx)

Name

Word

Bit [Unit] / Note

Reference

Servo On

OBC001 0

Alarm Clear

OBC000 6

Speed ("Feed" Speed)

OLC022

[10^3 R.U./minute (by default)]

Motion Command Code

OWC020

1=Position, 3=Home, 7=Jog, 8=Step

Position Reference

OLC012

[R.U.]

Abs/Inc Position Mode

OBC001 E

0=Abs, 1=Inc

Step Distance

OLC028

[R.U.]

Direction (Step,Jog)

OBC021 2

0=Fwd, 1=Rev

Acceleration

OWC00C

[ms to rated speed (FP7)] SVB: Use
OWC020=10 to send accel to
servopack Pn80B

Deceleration

OWC00D

[ms to rated speed (FP7)] SVB: Use
OWC020=11 to send accel to
servopack Pn80E

Motion Monitoring Registers (

I

Wxxxx)

Name

Word

Bit [Unit] / Note

Reference

Servo Alarm

ILC022

=0 when no alarm. Each bit
represents different alarm

Mtn Cmd Code confirm

IWC014

Main Power On

IBC001 4

Servo On Confirm

IBC001 3

Feedback Position

ILC008

[counts or Reference Units]

Advertising