Yaskawa VS-616G5 DeviceNet Communication Interface Card SI-M2 User Manual
Page 12

Page 12
VS-616G5 Option Instruction Manual: DeviceNet™ Communication Interface Card SI-M2
Supported Objects (cont.)
I/O Assembly Description
Note: All bytes in these I/O Assembly Instructions are in hexadecimal format.
Instance 1: Attributes Supported
Attribute
Get
Set
Description
Size
Default Value
3
X
—
At reference
Byte
0
4
X
X
Net reference
Byte
0
6
X
X
Drive mode
Byte
0
7
X
—
Speed actual
Byte
0
8
X
X
Speed reference
Byte
0
9
X
—
Current actual
Byte
0
15
X
—
Power actual
Byte
0
16
X
—
Input voltage
Byte
0
17
X
—
Output voltage
Byte
0
18
X
X
Accel time
Byte
10.0
19
X
X
Decel time
Word
10.0
20
X
X
Low speed limit
Word
0
21
X
X
High speed limit
Byte
100
22
X
X
Speed scale
Byte
0
23
X
X
Current scale
Byte
0
24
X
X
Torque scale
Byte
0
25
X
X
Process scale
Word
0
26
X
X
Power scale
Word
0
27
X
X
Voltage scale
Byte
0
28
X
X
Time scale
Byte
0
29
X
X
Reference from the net
Byte
0
DeviceNet
Basic Speed Control
Output
Instance
20
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit1
Bit 0
0
—
—
—
—
—
Fault
Reset
—
Run
Fwd
1
—
2
Speed Reference (Low byte)
3
Speed Reference (High byte)
DeviceNet
Extended Speed Control
Output
Instance
21
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit1
Bit 0
0
—
NetRef
NetCtrl
—
—
Fault
Reset
Run
Rev
Run
Fwd
1
—
2
Speed Reference (Low byte)
3
Speed Reference (High byte)