Djustments – Jordan Valve Mark 17X Series Flameproof Smart Positioner User Manual

Page 11

Advertising
background image

-11-

a

djustMents

Limit Switch Adjustments

1.

HIGH variable resistor adjusts the sensing point of the valve end point. For Direct Acting, it will sense 4mA

point, and for Reverse Acting, 20mA of the input signal will be the sensing point. Red LED will be lit upon

sensing.

2.

LOW variable resistor adjusts the sensing point of the valves zero point. For Direct Acting, it will send 20mA

point, and for Reverse Acting, 4mA of the input signal will be the sensing point. Red LED will be lit upon

sensing.

3.

If V+ and COM terminals are connected, electric current may be used on limit switch for an alarm or light

indicator as required.

4.

If V- and COM terminals are connected, electric voltage may be used on limit switch to receive a signal from

a computer.

5.

LS-ACTION, switch to change between Direct (DR), Reverse (REV) action.

6.

By adjusting the variable resistor, the limit switch operating range may be set. Turn Clockwise to widen

the range, and Counter Clockwise to shorten the range. As the range adjusts, the red LED will light

to indicate the completion of adjustments.

Variable Orifice Adjustments

Hunting may occur when the actuator volume is too small. In order to prevent hunting, orifice adjustments may be

made. By adjusting the orifice, the flow rate of the supply pressure may be adjusted. Use a flathead screwdriver to

make adjustments as required.