Connection: Double Acting Actuator,

Double acting type positioner is set to use the OUT1 and OUT2 ports. As the input signal increases the supply pres-

sure will be supplied through the OUT1 port.

Power Connections:

Ensure safety codes applicable to the location are adhered to as required.

-

When installing in hazardous locations, proper conduit tubing or pressure proof packing union must be

used. The compound charging box should be flameproof type and completely sealed.

-

Standard conduit entry tap is PF (G) 1/2"

-

Before connection the terminal, ensure proper safety precautions have been taken, and all power is com

pletely shut off. Do not open the cover while power to the positioner is live.

-

Positioners with PTM option must be supplied with 10~28V DC separately. For L/S option, separate 12-24V

DC must be supplied. Do not exceed 30V DC if both options are being utilized.

-

Ensure proper grounding of the positioner.

-

Ensure proper wiring is utilized in accordance to local codes and installation application. It is recommended

that shielded wiring be used to protect from electro-magnetic field and noise. Do not install the cable near

high noise environments, such as high capacity transformer or motor.