Measuring 3-Phase 4-Wire

(3 4W) Power Parameters:


In both un-balanced and balanced load cases, 3-Phase 4-Wire (3

4W) systems,

measure the phase-to-neutral powers kW

1,

kW

2

and kW

3

of each phase separately as

illustrated. System (total) power kW

Total

is the summation of all three phase-to-neutral

powers. That is:
kW

Total

= kW

1

+ kW

2

+ kW

3

(for both un-balanced and balanced load cases)


In balanced load cases, 3-Phase 4-Wire (3 4W) systems, the system (total) power
parameters can be simplified to three times of any of the phase-to-neutral powers. That
is:
kW

Total

= 3 x kW

1

(for balanced load cases only)

kVA

Total

= 3 x kVA

1

(for balanced load cases only)

kVAR

Total

= 3 x kVAR

1

(for balanced load cases only)