Measuring 3-Phase 3-Wire

(3 3W) Power Parameters:


In both un-balanced and balanced load cases, 3-Phase 3-Wire (3

3W) systems,

measure the power components kW

1

and kW

2

separately as illustrated. System (total)

power kW

Total

is the summation of the two measured power components. That is:

kW

Total

= kW

1

+ kW

2

(for both un-balanced and balanced load cases)


In balanced load cases, 3-Phase 3-Wire (3 3W) systems, the system (total) power
parameters can be achieved by the following expressions:
kW

Total

= kW

1

+ kW

2

(same as above)

kVA

Total

= √3 x kVA

1

(for balanced load cases only)

kVAR

Total

= √(kVA

Total2

- kW

Total2

)

(for balanced load cases only)