3 cable connections – ProSoft Technology MVI56-BAS User Manual
Page 226

Reference
MVI56-BAS ♦ ControlLogix Platform
User Manual
BASIC Module (DB/BAS Compatible)
Page 226 of 234
ProSoft Technology, Inc.
December 13, 2011
11.3 Cable Connections
The MVI56-BAS module has the following communication connections on the
module:
BASIC DH-485
BASIC PRT1
BASIC PRT2
Each of the above module connectors are RJ45 style. Short cable adapters are
provided to convert the RJ45 connections to DB-9. The following table shows the
pinout for the DH-485 connector:
RJ45 Pin #
DB-9 Pin #
Description
1
1
DCD
2
2
RXD
3
3
TXD
4
4
DTR
5
5
Logic Ground
6
6
DSR
7
7
RTS
8
8
CTS
9
Open
Shell
Shell
Earth Ground
The following table shows the pinout for both PRT1 and PRT2:
RJ45 Pin #
DB-9 Pin #
RS-232
RS-422
RS-485
1
1
DCD
TXD+
TXD/RXD+
2
2
RXD
RXD+
3
3
TXD
4
4
DTR
5
5
Common
Common
Common
6
6
DSR
RXD-
7
7
RTS
8
8
CTS
TXD-
TXD/RXD-
9
Open
Open
Open
Shell
Shell
Earth Ground
Earth Ground
Earth Ground