Reference

MVI71-GEC ♦ PLC 5 Platform

User Manual

Generic ASCII Ethernet Communication Module

Page 74 of 86

ProSoft Technology, Inc.

May 11, 2011

5.5

MVI71-GEC Configuration Data

This section contains a listing of the parameters and their definitions for the

MVI71-GEC module configuration file definition.

5.5.1 MVI71-GEC Server Communication Module Configuration

[Section]/Item

Value

Range

Description

[MODULE]

Module parameter definitions

Module Name:

0 to 80
characte

rs

This parameter assigns a name to the module that
can be viewed using the configuration/debug port.

Use this parameter to identify the module and the

configuration file.

[Section]/Item

Value

Range

Description

[Server 0]

Server definitions

Enabled:

Yes or

No

This parameter determines if the server will be
utilized by the module. If a value of "Yes' is entered,
the server will be used. Any other value will disable

the server.

Service Port Number:

1 to

65535

This parameter sets the TCP/IP service port for this
server. Each server can have its own unique

service port or can share the same number with

other servers.

Connection Timeout:

0 or
5000 to

65535

This parameter specifies the number of
milliseconds the server will permit the server to be

inactive after a connection is made before closing
the socket. This timeout period is reset on each

read or write packet. If the parameter is set to 0, the

connection will not timeout.

Connection Close Type:

0, 1 or 2 This coded parameter defines the personality of the

server after a connection is made. If the parameter

is set to 0, the socket will only be closed when a
request from the client is received or the connection

timeout is exceeded. If a value of 1 is selected, the

server will close the socket after it transmits a

single message. If a value of 2 is selected, the
server will close the socket after it receives a

message.

Swap Rx Data Bytes:

Yes or

No

This parameter is determines if the data received
by the server will have the byte order of the data

swapped. If the parameter is set to No, no byte

swapping will occur. If the parameter is set to Yes,
the odd byte will be swapped with the even byte in

each word of data received.

Swap Tx Data Bytes:

Yes or

No

This parameter is determines if the data to be
transmitted by the server will have the byte order of

the data swapped. If the parameter is set to No, no

byte swapping will occur. If the parameter is set to
Yes, the odd byte will be swapped with the even

byte in each word of data received.

Note: Add other [Server n] sections for each server to be utilized.