Led indicators, Base module leds, 6 led indicators – ProSoft Technology 5201-DFNT-ASCII User Manual

Page 29

Advertising
background image

LED Indicators

ASCII ♦ ProLinx Standalone

Generic ASCII Serial Communication Module

ProSoft Technology, Inc.

Page 29 of 40

July 7, 2008

6 LED

Indicators

In This Chapter

™

Base

Module LEDs................................................................................29

™

LEDs for Port 0 Serial Port .................................................................... 30

™

4101

Series LEDs ................................................................................. 30

Troubleshooting the operation of the DNP Slave port can be performed using
several methods.

The first and quickest is to scan the LEDs on the module to determine the
existence and possibly the cause of a problem. This section provides insight into
the operation of the Serial Port status LEDs. Information on the module's other
LEDs can be found in the ProLinx Reference Guide.

6.1

Base Module LEDs

LED State

Description

Off

Power is not connected to the power terminals. This LED is hardware
driven, so it only requires power to operate.

Power

Green Solid

Power is connected to the power terminals. Verify that the other LEDs
for operational and functional status.

Off Normal

operation.

Fault

Red Solid

A critical error has occurred. Program executable has failed or has
been user-terminated and is no longer running. Press Reset p/b or
cycle power to clear error. If not, use the Debug procedures described
later in this manual.

Off Normal

operation.

Cfg

Amber Solid

The unit is in the configuration mode. The configuration file is being
read and the unit is implementing the configuration values and
initializing the hardware. This will occur during power cycle, or after
pressing the reset button. It also occurs after a cold/warm boot
command is received.

Off Normal

operation.

Flashing

An error condition has been detected and is occurring. Check
configuration.

Err

Solid Red

This condition is indicative of a large number of errors in the
application interface communications. The module's error flag is
cleared at the start of each command (master/client) or receipt of data
(slave/adapter/server).