Sub-function codes supported, 00 return query data, Example and state diagram – ProSoft Technology 5201-MNET-ASCII User Manual

Page 63

Advertising
background image

MNET ♦ ProLinx Gateway

Modbus Protocol Specification

Modbus TCP/IP Interface Module

Driver Manual

ProSoft Technology, Inc.

Page 63 of 78

September 1, 2010

4.7.1 Sub-function codes supported

Only Sub-function 00 is supported by the MNET gateway.

The data passed in the request data field is to be returned (looped back) in the
response. The entire response message should be identical to the request.

00 Return Query Data

Sub-function

Data Field (Request)

Data Field (Response)

00 00

Any

Echo Request Data

Here is an example of a request to remote device to Return Query Data. This
uses a sub-function code of zero (00 00 hex in the two-byte field). The data to be
returned is sent in the two-byte data field (A5 37 hex).

Example and state diagram

Request

Response

Field Name

(Hex)

Field Name

(Hex)

Function

08

Function

08

Sub-function Hi

00

Sub-function Hi

00

Sub-function Lo

00

Sub-function Lo

00

Data Hi

A5

Data Hi

A5

Data Lo

37

Data Lo

27

The data fields in responses to other kinds of queries could contain error counts
or other data requested by the sub-function code.