Zero clearance fireplace installation, Initial installation – Enviro C-11212 User Manual

Page 17

Advertising
background image

NOTE: If the Sienna unit is pulled

out of its installation, and the vent

air intake system is disconnected

for any reason, ensure that the

vent-air intake pipes are re-sealed

with high-temperature sealant

or silicone and reconnected with

three (3) sheet metal screws

evenly spaced.
IMPORTANT: The Sienna is to be

vented only with vertical venting

– no horizontal.

2ft (0.6m)

Minimum

3ft (0.9m)

Minimum

Within

10ft (3m)

Roof ridge or

any other portion

of a building

Figure 21: Roof Clearances.

Table 3: Vent termination clearances

Minimum Clearance

Description

3 ft (0.9 m)

Clearance above the highest point where it passes through a roof surface, refer

to Figure 21.

24 in (0.6 m)

Clearance above a roof ridge, any other portion of a building, or any other ob-

struction within a horizontal distance of 10 feet (3 m), refer to Figure 21.

5 ft (1.5 m)

Clearance for a vent or chimney above either the highest connected appliance

drafthood outlet, or flue collar.

6 ft (1.83 m)

Clearance to mechanical air supply inlet.

3ft (0.9m)

Clearance to each side of center line extended above meter/regulator assembly.

6 ft (1.83 m)

Radial clearance around service regulator vent outlet.

12 in (30 cm)

Clearance above grade, verandah, porch, deck, or balcony.

3 ft (0.9 m)

Clearance to a building opening or combustion air inlet of another appliance,

except with the approval of the authority having jurisdiction for the following

reduced clearances.

9 in (0.23 m)

Exception for inputs up to and including 50,000 Btu/h (15kW)

12 in (0.3 m)

Exception for inputs exceeding 50,000 Btu/h (15kW) but not exceeding 100,000

Btu/h (30kW)

Z

ERO

C

LEARANCE

F

IREPLACE

I

NSTALLATION

:

The metal floor of the ZC solid fuel firebox can be removed to allow the installation of the insert. THE

CLEARANCE TO COMBUSTIBLE MATERIAL UNDER THE INSERT IS 1⁄2” (13mm). YOU MUST USE THE

LEVELING LEGS TO RAISE THE INSERT A MINIMUM OF 1⁄2” (13mm) IF THE UNIT IS TO BE INSTALLED

ON COMBUSTIBLE MATERIAL. The sidewalls and top structure of the solid fuel firebox cannot be altered

with the exception of removable dampers and baffles. THE ORIGINAL FIREPLACE MAY NEVER BE

RETURNED TO SOLID FUEL USE IN THIS CONDITION.
IMPORTANT: If the factory-built fireplace has no gas access hole(s) provided, an access hole of 1.5 inch

(37.5 mm) or less may be drilled through the lower sides or bottom of the firebox in a proper workmanship

like manner. This access hole must be plugged with non-combustible insulation after the gas supply line

has been installed. Cutting any sheet-metal parts of the fireplace, in which the gas fireplace insert is to

be installed, except as tested for the floor is prohibited.

Initial Installation

QUALIFIED INSTALLERS ONLY

17

Advertising
This manual is related to the following products: