Gas line connection, Initial installation, Never use an open flame for leak testing – Enviro C-11212 User Manual

Page 19: Qualified installers only g

Advertising
background image

Initial Installation

QUALIFIED INSTALLERS ONLY

G

AS

L

INE

C

ONNECTION

:

Warning: Only persons licensed to work with gas piping may make the necessary gas connections to

this appliance.

Gas Line Connection:
•This fireplace is equipped with a certified flexible pipe located on the right side of the unit, terminating

in a 3⁄8” male NPT fitting. Consult the local authorities for local codes or use the CAN/CGA B149 (1 or 2)

installation code in Canada. In the US, gas installations follow either local codes or the current edition of

the National Fuel Gas Code ANSI Z223.1.
•The efficiency of this unit is a product thermal efficiency rating determined under continuous operating

conditions and was determined independently of any installed system.

The appliance and its appliance main gas valve

must be disconnected from the gas supply piping

system during any pressure testing of that system

at test pressures in excess of 1⁄2 psi (3.5 kPa).

The appliance must be isolated from the gas

supply piping system by closing its equipment

shutoff valve during any pressure testing of the

gas supply piping system at test pressures equal

to or less than 1⁄2 psi (3.5 kPa).
The unit must be isolated from the gas supply

piping system by closing its individual manual

shut off valve during any pressure testing of the

gas supply piping system at pressures equal to

or less than 1⁄2 psig (3.45 KPa).

O

L I

T

P

TP

TH

TP

TH

IN

OU

T

H

I

LO

N

OF

O

F

LI

P

T O

��������

�������� ���

�����

�������� ���

������

����

����� ����������

�����

��� �������

����

Main Burner

Natural Gas

Propane Gas

Orifice:

#32 DMS

#49 DMS

Venturi Setting:

1⁄2” Min.

7⁄8” Min.

Manifold Press:

3.8 W.C. (0.95 KPa) 11.0 W.C. (2.74 KPa)

Min. Manifold Press: 1.2 W.C. (0.30 KPa) 2.7 W.C. (0.67 KPa)
Max. Supply Press:

7.0 W.C. (1.74 KPa) 13.0 W.C. (3.28 KPa)

Min. Supply Press:

5.0 W.C. (1.24 KPa) 12.0 W.C. (2.98 KPa)

Max. Input:

41,000 BTU/hr

(12.0 KW)

41,000 BTU/hr

(12.0 KW)

Min. Input:

23,000 BTU/hr

(6.7 KW)

21,000 BTU/hr

(6.1 KW)

Always check for gas leaks with a soap

and water solution after completing the

required pressure test.

TO TEST VALVE PRESSURES:

The pressure taps are located on the top right

of the valve (see Figure 24).
• Turn set screw one (1) turn counter-clockwise

to loosen.

• Place

5

/

16

in (8 mm) I.D. hose over the

pressure taps.

• Check pressures using a manometer.
• When finished, release pressure, remove

hose and tighten set screw.

NEVER USE AN OPEN FLAME FOR LEAK TESTING.

Figure 24: Fully labeled gas valve.

Table 5: Orifice and Pressure Information.

19

Advertising
This manual is related to the following products: