B. Secure the Fireplace

• Position the Fireplace

This fireplace may be placed on either a combustible or

noncombustible continuous flat surface. Follow the in-

structions for framing in Section 3.D. Slide the fireplace

into position. Be sure to provide the minimum air clear-

ance at the sides and back of the fireplace assembly.

See Section 3.B.

Included with your fireplace you will find two metal

hearth strips measuring approximately 26 in. x 4 in.

(660 mm x 102 mm). These strips are used to provide

added protection where the fireplace and the hearth ex-

tension meet.
Slide each metal strip 2 in. (51 mm) under the front

edge of the fireplace. The individual pieces must over-

lap each other by 1 in. (25 mm) minimum in the middle

of the fireplace to provide continuous coverage of the

floor. See Figure 4.4. These metal strips should extend

from the front and sides of the fireplace opening by 2 in.

(51 mm).

Note: When elevating the fireplace above the hearth

extension the front of the elevated platform must be

protected with a protective metal hearth strip as shown in

Figure 4.6.

Raised Platform

Floor

2 in.

(51 mm)

1 in. (25 mm) min.

overlap

2 in.

(51 mm)

Top piece must overlap

bottom piece

Figure 4.5 Protect the Front of an Elevated Platform

• Level the Fireplace

Level the fireplace side-to-side and front-to-back. Shim

with noncombustible material, such as sheet metal, as

necessary. Secure the fireplace (using the nailing flang-

es located on either side of the fireplace) to the vertical

framing.

Important: To ensure proper fit of the glass doors, check

the fireplace opening for square. Measure diagonal

distances of the opening to make sure they are equal.

If they are not, continue to shim the fireplace until those

diagonals are equal.

Protective metal strips are placed 2 in. (51 mm) under the

front of the fireplace and must extend beyond the front

and sides of fireplace opening by 2 in. (51 mm).

1 in. (25 mm)

overlap

Figure 4.4 Position the Protective Metal Hearth Strips

• Place the Protective Metal Hearth Strips

Fire Risk!

• Prevent contact with sagging, loose

insulation.

• Do NOT install against vapor barriers or

exposed insulation.

WARNING

Fire Risk!

• Metal hearth strips MUST be installed.
Sparks or embers may ignite flooring.

WARNING