Outdoor Lifestyles by Hearth & Home Technologies Inc. • Montana US-CAN • 4039-156 Rev P • 10/12

18

6

Complete the Enclosure

Figure 6.1 Multiple Chimneys

A. Chimney Termination

Chimney Termination Requirements (See Figure 6.1)

• Must have a cap approved and listed for this fireplace system

• Must not be located where it will become plugged by snow or other material

• Must terminate at least 3 ft (914 mm) above the roof

and at least 2 ft (610 mm) above any portion of the roof within 10 ft

(3.05 m)

• Must be located away from trees or other structures

Slanted Roofs

Flat Roofs

Chimney must

extend 3 ft (.9 m)

above the roof

Chimney must extend 2 ft (.6 m)

above any portion of the roof or

adjacent structures within

10 ft (3 m) of the chimney

Chimney must

extend 3 ft (.9 m)

above the roof

Chimney must extend 2 ft (.6 m)

above any portion of the roof or

adjacent structures within

10 ft (3 m) of the chimney

Multiple Chimney Locations

A

B

6 in. (minimum) up to 20 in.

152 mm/508 mm

18 in. minimum

457 mm

20 in. and over

0 in. minimum

Gas, Wood or Fuel Oil

Termination Cap

Wood

Minimum

(See

illustration

above)

B

Gas

Termination

Cap **

A *

Perpendicular W

all

*

If using decorative cap cover(s), this distance may need to be

increased. Refer to the installation instructions supplied with the

decorative cap cover.

**

In a staggered installation with both gas and wood terminations, the

wood termination cap must be higher than the gas termination cap.