Caution, Warning, D. install the ceiling firestops – Hearth and Home Technologies MONTANA 42 EN User Manual

Page 16

Advertising
background image

Outdoor Lifestyles by Hearth & Home Technologies Inc. • Montana US-CAN • 4039-156 Rev P • 10/12

16

C. Assemble the Chimney Sections

Attach either a straight chimney section or an offset to the

top of the fireplace (depending on your installation require-

ment). Chimney sections are locked together by pushing

downward until the top section meets the stop bead on the

lower section.
The inner flue is placed to the inside of the flue section below

it. The outer casing is placed outside the outer casing of the

chimney section below it. See Figure 5.2.

D. Install the Ceiling Firestops

• Mark and cut an opening in the ceiling for the ceiling

firestop being used. See Figure 5.3.

• Frame the opening with the same size lumber used in the

ceiling joists.

• Install the ceiling firestop.

Note: The ceiling firestop MUST be nailed to the bottom

of the ceiling joists EXCEPT when the space above is

uninsulated and the attic insulation shield is not being used

(see Figure 5.5). When the attic insulation shield is used

the ceiling firestop may be above or below the joist of an

insulated ceiling.

Note: You must provide support for the pipe during

construction and check to be sure inadvertent loading has

not dislodged the chimney section from the fireplace or at

any chimney joint.

Note: Inner flue and outer liner sections cannot be

disassembled once locked together. Plan ahead to ensure

the proper installation height is achieved with the selected

chimney components.

• Ceiling firestops must be used at ceiling/floor.

• Chase construction requires ceiling firestops at each

floor or every 10 ft ( 3.05 m) of clear space.

• Use same dimensional lumber as joists.
Ceiling firestop slows spread of fire and reduces cold air

infiltration.

CAUTION

Figure 5.2 Assembling Chimney Sections

Fire Risk
Do NOT install substitute or damaged

chimney components.

• MUST use chimney system described in

this manual.

• NO OTHER chimney components may

be used.

Substitute or damaged chimney components

may impair safe operation.

WARNING

ROOM ABOVE (non-insulated ceiling)

ATTIC ABOVE (insulated ceiling)

B

A

Ceilng firestop from

bottom

Ceiling firestop from

top

Note:

Use same dimensional lumber for framing

ceiling firestop and joists.

Figure 5.3 Installing the Ceiling Firestop

Catalog #

A

B

in.

mm

in.

mm

FS538

17

432

17

432

FS540

17

432

26

660