C. Bedroom Installation in Canada
This model MUST NOT be vented into a vent

system installed exterior to a building. The part of

the vent system above the roof line can be exterior

to the building.

D. Vent Termination

WARNING: MAJOR U.S. BUILDING

CODES SPECIFY MINIMUM

CHIMNEY AND/OR VENT HEIGHT

ABOVE THE ROOF TOP. THESE

MINIMUM HEIGHTS ARE

NECESSARY IN THE INTEREST OF

SAFETY. FIGURE 6 AND TABLE

SHOW MINIMUM HEIGHTS,

PROVIDED THE TERMINATION CAP

IS AT LEAST 8-FEET FROM A

VERTICAL WALL.

ROOF PITCH

H (MIN.) FT.

FLAT TO 6/12

1.0

6/12 TO 7/12

1.25

OVER 7/12 TO 8/12

1.5

OVER 8/12 TO 9/12

2.0

OVER 9/12 TO 10/12

2.5

OVER 10/12 TO 11/12

3.25

OVER 11/12 TO 12/12

4.0

OVER 12/12 TO 14/12

5.0

OVER 14/12 TO 16/12

6.0

OVER 16/12 TO 18/12

7.0

OVER 18/12 TO 20/12

7.5

OVER 20/12 TO 21/12

8.0

Figure 6. Vent Termination

H (MIN.)-MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING

H (MIN.)-MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING

VENT CAP

LOWEST DISCHARGE OPENING

12

X

ROOF PITCH IS X/12