3-12

P/N 480-0005-00-15

Chapter 3: Installation

Figure 3-9 Strip away wire

3. Insert the wire into the connector in the position shown in Figure 3-10.

Figure 3-10 Connector position

4. Secure by tightening the clamping screw with a straight blade screwdriver of size 0.023x 0.137 (0.6 x

3.5mm). Screws must be torqued between a minimum of 4.4 lbs in (0.5 Nm) and a maximum of 5.3 lbs in
(0.6 Nm).

WARNING:

Do not over torque the screws.

5. Repeat steps 2-4 for the RTN and -48V source, respectively, in the same sequence shown in Figure 3-11.

Figure 3-11 Wire connection sequence

6. Once the connections are complete between the DC feed(s) and the Tenor CMS power plug (s), insert the

plugs into the power receptacles.

7. Secure the power plugs to each of the power receptacles by torquing the screws in the face of the plug to

between a minimum of 4.4 lbs in. (0.5Nm) and a maximum of 5.3 lbs in. (0.6Nm) with the same screw-
driver. See Figure 3-12. Plug and secure both power plugs, even if only one DC power feed is used.

Figure 3-12 Plug and secure power plugs

0.25" (7.0mm)

DC Power Wire Strip Length

10 - 14 AWG

-48 |RTN|

Secure both screws in the face of the Plug, with a straight
blade screwdriver of size 0.023" x 0.137", (0.6 x 3.5mm)

Caution: Screws must be torqued between a minimum of
4.4 lbs.in,(0.5 Nm) and a maximum of 5.3 lbs. in (0.6 Nm)