Installation 20

When using an ERM, set the Battery Charge Level switch (DIP switch 3) to the down position, increasing

the UPS charger output and charging the ERM faster.

CAUTION:

Do not set the Battery Charge Level switch to the down position without an ERM

connected. There is a risk of damaging the internal battery system of the UPS.

NOTE:

DIP switch 4 is inactive and does not affect UPS operation regardless of the position.

NOTE:

An asterisk (*) indicates the default setting.

Output

voltage

Input

voltage

range

DIP switch 1 DIP switch 2 DIP switch 3 DIP switch 4

R/T2200
NA/JPN/TW

N

120 V* (NA)

108–127 V Up

Up

Up*

Up

110 V

99–116 V Up

Down

100 V*
(JPN/TWN)

90–106 V Down

Up

120

V 108–127

V Down Down Down Down

R/T2200 INTL 230 V

20–7243 V Up

Up

Up*

Up

230 V* (INTL) 207–243 V Up

Down

220 V

198–233 V Down

Up

240

V 216–254

V Down Down Down Down