Connecting the repo port – HP T2200 User Manual
Page 22
Advertising

Installation 22
CAUTION:
Using a USB to serial converter cable will damage the UPS.
Connecting the REPO port
WARNING:
To meet the requirements stated in NEC (NFPA 70) Articles 645-10 and 645-11,
a UPS installed in a computer equipment room must be connected to a REPO circuit.
IMPORTANT:
The remote switch must be in the Off (open) position to enable power to the
output receptacles.
NOTE:
Wire the connector block using stranded, nonshielded wire (AWG #22 - #18, or
equivalent).