Top vent - vertical termination no elbow, 3 ft. min. (914 mm) installing flue restrictor – Hearth and Home Technologies 8000TR-OAK User Manual

Page 27

Advertising
background image

Heat & Glo • 8000TR-OAK, 8000TR-OAK-IPI, 8000TRLP-OAKIPI • 2057-900 Rev. P • 11/08

27

Top Vent - Vertical Termination

No Elbow

Figure 7.6

Note: If installing a vertical vent/termination off the top of the
appliance, the fl ue restrictor should be used.

V

1

V

1

= 50 ft. Max. (15.2 m)

V

1

= 3 ft. Min. (914 mm)

Installing Flue Restrictor

1. Remove Exhaust Shield using a 1/4 in. nut driver by

removing the three screws securing it in place (see
Figure 7.7).

Figure 7.7

EXHAUST

SHIELD

FLUE

RESTRICTOR

2. Break the Flue Restrictor into two pieces. Do this by

bending the part back and forth until it breaks (see
Figure 7.8).

3. Match the amount of vertical in the system with the chart

to fi nd the appropriate position to set the Flue Restrictor
(see Figure 7.9).

- CHART -

Vertical

Top Vent

NG

Top Vent

LP

Rear Vent

NG

Rear Vent

LP

4’

1-1

No Restrictor No Restrictor No Restrictor

8’

2-2

1-2

1-1

No Restrictor

15’

3-3

3-2

2-2

1-2

20’

3-4

3-3

3-3

2-3

25’

3-4

3-3

3-3

2-3

30’

4-4

3-4

3-4

3-3

35’

4-4

3-4

3-4

3-3

40’

5-4

4-4

4-4

3-4

45’

5-4

4-4

4-4

3-4

50’

5-4

4-4

4-4

3-4

Figure 7.9

Figure 7.10

4. Center the Flue Restrictor on vent and secure in place

by using two self-tapping screws (see Figure 7.10).

Figure 7.8 Flue Restrictor

BREAK

HERE

1 2 3 4 5

SETTING

1 2 3 4 5