Voltage configuration led is green, Output load level led is red or flashing red, Battery charge led is red – HP R2200 User Manual

Page 44

Advertising
background image

Troubleshooting 44

If the Battery Charge LED is also red:

a.

Save your work, and power down the UPS ("

Powering down the UPS

" on page

36

).

b.

After the blackout or brownout is over, power up the UPS ("

Powering up the UPS

" on page

27

).

c.

Allow the UPS batteries to charge for 24 hours.

If the Battery Charge LED is also yellow or green:

a.

Consider saving your work and powering down the UPS (on page

36

). If the blackout or

brownout is prolonged, the Battery Charge LED turns red as the UPS batteries near depletion.

b.

After the blackout or brownout is over, power up the UPS ("

Powering up the UPS

" on page

27

).

c.

Allow the UPS batteries to charge for 24 hours.

Voltage Configuration LED is green

Action: The UPS is automatically correcting high or low AC voltage on the utility line. No action is

required.

Output Load Level LED is red or flashing red

Action:

1.

Remove one or more load devices to reduce the power requirements.

2.

Initiate a self-test ("

Initiating a self-test

" on page

35

).

3.

If the condition persists, verify that the load devices are not defective.

Battery Charge LED is red

Action:
If the Power LED is flashing green:

a.

Save your work, and power down the UPS ("

Powering down the UPS

" on page

36

).

b.

After the blackout or brownout is over, power up the UPS ("

Powering up the UPS

" on page

27

).

c.

Allow the UPS batteries to charge for 24 hours.

If the Power LED is green:

a.

Continue to let the batteries charge until the Battery Charge LED is green.

b.

Initiate a self-test ("

Initiating a self-test

" on page

35

).

Advertising