Heatilator • RAVE4013I-C • 2293-900 Rev. E • 2/13

Figure 7.4

Top Vent - Horizontal Termination

Venting with 1 elbow

H

1

V

1

V Minimum

H

1

Maximum

RAVE4013I-C

90 Elbow

1-1/2 ft.

457mm

1 ft.

305 mm

3 ft.

914 mm

2 ft.

610 mm

5 ft.

1.5 m

3 ft.

914 mm

7 ft.

2.1 m

4 ft.

1.2 m

14 ft.

4.3 m

H MAX. =14 ft. (4.3 m)

V + H MAX. = 40 ft. (12.2 m)

Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around venting and fi restop systems.
• Install wall shield and ceiling fi restops as specifi ed.
Failure to keep insulation or other material away from vent pipe may cause fi re.

WARNING

Note: Use SLP Series
components only.

Note: There MUST be a 25%
reduction in total H when using
fl ex vent except when using the
simple up and out installation
(see Figure 7.3).

CAUTION: The SLP-HRC-SS and SLP-HRC-ZC-SS
termination caps are not approved for use with pro-
pane (LP) fuel. May lead to elevated glass temper-
ature that may cause tempered glass breakage.