SERvICING INSTRUCTIONS

FAULT FINDING ChARTS

27

FLAME FAILURE FUNCTIONAL CHECK

PILOT WILL NOT STAY LIT OR FIRE GOES OUT

If the fire goes out in use continually, this may mean that the

oxygen depletion sensor has been activated. The fire should not be used

until the cause has been found and rectified.

Ensure there is no debris around the pilot assembly, e.g. coal, soot, etc.

Check for fluff in the pilot aeration hole. See diagram 10.

Light the pilot and keep the control knob pushed in at least

10 seconds before letting go

With the pilot

running is the

gas pressure as

stated on the

data badge?

Is the pilot

flame of the

correct length?

See diagram 7.

Is thermocouple

connection good

in back of valve

Replace

ODS unit

Change the

ODS unit

SySTEM O.K

Tighten the

connection and

retry

With the fire

running on full is

the gas at the

pressure stated

on the data badge

Problem is with

the pipe work or

fittings which lead

to the fire. Correct

and retry

Run for 60 secs.,

turn off, time

interval until mag

unit shuts with a

click. Is this greater

than 7 seconds?

Run for 60 secs.,

turn off, time

interval until mag

unit shuts with a

click. Is this greater

than 7 seconds?

Will the pilot

stay lit?

Will the pilot

stay lit?

Change

mag unit

YES

NO

NO

NO

NO

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES