Using this chapter – GE GEFanuc Automation Programmable Control Products TCP/IP Ethernet Communications for the Series 90t-70 PLC GFK-1004B User Manual

Page 173

Advertising
background image

6

6-2

TCP/IP Ethernet Communications User’s Manual – January 1996

GFK-1004B

Also, when displaying a PLC Fault Table entry on the Logicmaster 90-70, striking
<CTRL -F> will display an additional line of numeric data on the Message Line
(third line from the top). For GEnet Ethernet Interfaces the leftmost 16 digits of the
long string of digits on the right half of the Message Line show the corresponding
GEnet log Events and Entries 2, 3, and 4 (in that order). This information can be
used to refer directly to detailed fault descriptions in this chapter (Table 6-10)
without using a GSM.

For detailed information about these tools, refer to the appropriate references in the
table below.

Table 6-1. Ethernet Interface Diagnostic Tools

БББББББ

БББББББ

Diagnostic Tool

БББББББББББББББ

БББББББББББББББ

Description

БББББББ

БББББББ

Reference

БББББББ

БББББББ

LEDs

БББББББББББББББ

БББББББББББББББ

Visual observation of Ethernet Interface

БББББББ

БББББББ

Chapters 2, 6

БББББББ

Log

БББББББББББББББ

Access from Station Manager

БББББББ

Chapters 5, 6

БББББББ

БББББББ

Tallies

БББББББББББББББ

БББББББББББББББ

Access from Station Manager

БББББББ

БББББББ

Chapter 5

БББББББ

БББББББ

БББББББ

PLC Fault Table

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

Ethernet Interface exceptions logged with CPU

БББББББ

БББББББ

БББББББ

Chapter 6
Also GFK-0265

Using this Chapter

This chapter contains five troubleshooting sections that correspond to the five main
states of the Ethernet Interface.

If you have a problem, first identify in which state the problem occurred. Then, go to
the corresponding section in this chapter for further information.

The following tables are included to assist you in troubleshooting.

H LED Display Codes - Tables 6-2 through 6-6.
H Troubleshooting with ONLINE LED OFF - Tables 6-7.
H Troubleshooting with ONLINE LED ON - Table 6-8.
H Log Events Codes - Tables 6-9 and 6-10.

The following information indicates the state of the Ethernet Interface:

1.

Power-Up State

- The board is executing power-up diagnostics.

H The MODULE OK LED is BLINKING fast or OFF.
H The ONLINE LED is OFF.
H The STATUS OK LED is BLINKING or OFF.

In the power-up state, the Station Manager and the Restart pushbutton are
inoperative.

2.

Soft Switch Entry State

- Soft Switch configuration may be (in some cases must be)

entered via the Logicmaster 90-70 Configurator or the Ethernet Interface local
Station Manager (when the Ethernet Interface is not configured in the CPU).

H The MODULE OK LED is BLINKING slowly.
H The ONLINE LED is OFF.
H The STATUS OK LED is OFF.