GE GEFanuc Automation Programmable Control Products TCP/IP Ethernet Communications for the Series 90t-70 PLC GFK-1004B User Manual

Page 174

Advertising
background image

6

6-3

GFK-1004B

Chapter 6 Troubleshooting

A NODE command at the Station Manager will indicate “Soft Switch Entry Utility”.
The Station Manager prompt in this case is an asterisk (“*”).

3.

Field Network Test State

- Test frames may be exchanged with other nodes on the

network, using a factory-set configuration.

H The MODULE OK LED is ON.
H The ONLINE LED may be ON, OFF, or BLINKING.
H The STATUS OK LED may be ON or OFF.

A NODE command at the Station Manager will indicate “Field Network Test Utility”.
The Station Manager prompt in this case is a dollar sign (“$”).

4.

Loader State

- The communications software must be loaded or is being loaded.

H The MODULE OK LED is ON.
H The ONLINE LED may be ON, OFF, or BLINKING.
H The STATUS OK LED is BLINKING.

A NODE command at the Station Manager will indicate “Software Load Utility”.
There is no Station Manager prompt while in the loader. If the Ethernet Interface is
looking for a download from the serial port, repeated “ipl“ messages will be
displayed at the Station Manager terminal.

5.

Operational State

- The communications software has been loaded, and is running.

H The MODULE OK LED is ON.
H The ONLINE LED may be ON, OFF, or BLINKING.
H The STATUS OK LED may be ON or OFF.

A NODE command at the Station Manager will identify the node without indicating
any of the other “special” states. The default Station Manager prompt in this case is
a greater-than sign (“>“).

Advertising