The figure and text below explains how a Communications Request is executed. The
figure specifically illustrates the operation of an Establish Read Channel Command.

Client

Series 90–70

PLC CPU

Backplane

Ethernet
Interface

Server

Series 90 PLC

LAN

Power flows to COMMREQ
in ladder program

Command Block sent to
Interface

Verify
Command Block
and set up channel
to server PLC

Read Request

Data

Data

Read Request

Data

Data

Client

Data

Data

COMMREQ
Status Word

Return COMMREQ
Status Word (CRSW)
to CPU

.
.
.

.
.
.

Read Request

Data

Data

Data

Pulse Data Transfer bit

Pulse received

Pulse Data Transfer bit

Pulse received

Pulse Data Transfer bit

Pulse received

Data

Domain of a channel

Domain of a TCP connection

Figure 4-2. Operation of the Communications Request for an Establish Read Channel-
Command

1.

A Communications Request begins when there is power flow to a COMMREQ func-
tion in the client PLC. At this time, the Command Block data is sent from the PLC
CPU to the Ethernet Interface.

2.

For the Establish Read Channel Channel command, the COMMREQ Status word
(CRS word) is returned immediately if the Command Block is invalid. If the syntax is
correct, then the CRS word is returned after the next significant event: upon failure to
establish a channel correctly and in a timely manner or upon the first successful trans-
fer of data.

Once the channel is successfully set up to the server PLC, the Ethernet Interface
performs the periodic reads as specified in the Command Block.