C

TCP/IP Ethernet Communications User’s Manual – January 1996

C-6

GFK-1004B

6.

Text similar to that shown below will be displayed on the terminal after the
diagnostics are run. The Soft Switch Entry Utility banner will appear only if the
Ethernet Interface is in the Soft Switch Entry state. The CHSOSW command may be
used in any of the Ethernet Interface states.

IC697 PLC Factory LAN Interface

Copyright (c) 1990-1995. All rights reserved

PROM version 2.00 (xxAx) Ethernet

IP address = 3.16.18.47

MAC address = <<08001901001f>> MAC default = <<08001901001f>>

EM7A2

<<< Soft Switch Entry Utility >>>

7.

A “*” or other prompt character will be displayed on the terminal.

8.

To display the current values of the Soft Switches, enter the command SOSW.

9.

Set the values of the Soft Switches by entering the CHSOSW command. (Refer to
Chapter 4, Station Manager, for a detailed definition of the command syntax.)

The new values of the Soft Switches will be displayed. A typical CHSOSW command
for the Ethernet Interface is shown below:

* chsosw mac 020106000001 mms dc

<<< Soft Switch Data >>>

Config. Mode: MMS-ETHERNET

MAC Address = <<08001901001f>> (default used)

Load source = Serial

Network Online = Online after power up

Backplane Online = Online after power up

Network doad addr = <<090060000000>> (default used)

MMS Enable = Don’t Care *

Pgmr Enable = Don’t Care *

Source of Soft Switches: Internal Backup

Updating, please wait ...

* Not used by the TCP/IP Ethernet Interface.

10. If the Soft Switch data displayed in the CHSOSW command is correct for the station,

press the LAN Interface Restart button to cause the new Soft Switch values to take
effect. If the values shown are not what you want, repeat step 10, supplying the
proper values.

Caution

Soft switch values set by the

CHSOSW Station Manager command will

be overridden by values configured in the Logicmaster 90-70
Configurator.