12 generators and gts transfer switches, 13 control circuit interconnections – Generac 04077-01 User Manual

Page 16

Advertising
background image

14 Generac

®

Power Systems, Inc.

1.12 GENERATORS AND GTS

TRANSFER SWITCHES

Guardian generators (this DOES NOT APPLY to single-

phase sound attenuated units) may be installed with

either a prepackaged transfer switch or with a stan-

dard GTS-type automatic transfer switch (Figure

1.11). You can do this by connecting generator control

console terminals 178 and 183 to identically num-

bered terminals in the GTS switch. Turn dip switch #2

“Remote Not Auto” to the ON position on the generator

control printed circuit board.

NOTE:

The enclosure roof will need to be removed to gain
access to the printed circuit board.

When a Guardian generator is installed with a stan-

dard GTS-type switch, solid-state circuit boards in

the transfer switch control automatic operation.

For automatic operating sequences, parameters

and timing, refer to the appropriate GTS transfer

switch manual.
Automatic operation for Guardian generators

installed with prepackaged transfer switches is

controlled by a control module circuit board in the

control panel. Refer to the “Operation” section of

this manual.

1.13 CONTROL CIRCUIT

INTERCONNECTIONS

For 6 kw, 8 kW and 10 kW units (not including

sound attenuated), these interconnections consist

of “Utility” and leads 23 and 194 (see Figure 1.9,

Page 13). These four leads must be routed in con-

duit that is separate from the generator AC power

leads. Control lead functions may be briefly

described as follows:
1. Utility 1 and Utility 2: Deliver utility source power

to the generator's logic circuit board.

2. Leads 23 and 194: After the generator starts, the

logic circuit board in control panel delivers a

“transfer” signal via these two leads.

• When logic circuit board action closes this circuit,

it causes transfer switch main contacts to activate

and connect load circuits to generator output.

• When utility source voltage is restored, logic board

opens leads 23 and 194 circuit. Loads are then

transferred back to utility circuit.

NOTE:

Recommended size of control circuit leads (Utility
1 and 2, and 23 and 194) is No. 14 AWG stranded
copper wire.

Section 1 — Installation

Guardian Air-cooled Generators

Figure 1.11 – Interconnection With GTS Transfer Switch (100A, y-type)