2 fuel consumption, 3 fuel pipe sizing, 4 reconfiguring the fuel system – Generac 04077-01 User Manual

Page 8

Advertising
background image

6

Generac

®

Power Systems, Inc.

With LP gas, use only the vapor withdrawal system.
This type of system uses the vapors formed above the liq-

uid fuel in the storage tank.
The engine has been fitted with a fuel carburetion sys-

tem that meets the specifications of the 1997 California

Air Resources Board for tamper-proof dual fuel sys-

tems. The unit will run on natural gas or LP gas, but it

has been factory set to run on natural gas. Should the

primary fuel need to be changed to LP gas, the fuel sys-

tem needs to be reconfigured. See Section 1.6.4 (Page

6) for instructions on reconfiguration of the fuel system.
Recommended fuels should have a Btu content of at

least 1,000 Btus per cubic foot for natural gas; or at

least 2,520 Btus per cubic foot for LP gas. Ask your fuel

supplier for the Btu content of your fuel.
Fuel pressure for both natural gas and liquid propane

(LP) vapor set ups MUST be 11 inches to 14 inches of

water column (0.6 psi) at all load ranges.

1.6.2 FUEL CONSUMPTION

See the following chart for fuel supply requirements at

half and full load for both natural gas and LP vapor.

*Natural gas is in cubic feet per hour.

**LP is in gallons per hour/cubic feet per hour.

Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even the
slightest spark can ignite such fuels and cause
an explosion. No leakage of fuel is permitted.
Natural gas, which is lighter than air, tends to
collect in high areas. LP gas is heavier than air
and tends to settle in low areas.

1.6.3 FUEL PIPE SIZING

See the following chart for proper sizing of fuel supply

piping. Insufficient fuel pipe size can cause hard start-

ing, poor engine performance and inability to carry

load.

NG and LP Vapor Pipe Sizing Chart:

1.6.4 RECONFIGURING THE FUEL SYSTEM

To reconfigure the fuel system from NG to LP,

follow these steps:
1. Remove the carburetor fuel hose from the natural

gas port of the fuel load block and the brass fit-

ting (Figure 1.2).

2. Remove the blanking plug from the LP port of the

load block (Figure 1.2).

Figure 1.2 – Natural Gas Setup`

Section 1 — Installation

Guardian Air-cooled Generators

Model #

Nat. Gas (*)

LP Vapor (**)

1/2 Load Full Load

1/2 Load

Full Load

6 kW

74.1

105.3

0.86/31.30 1.08/39.30

8 kW

79.7

140.0

1.07/38.94 1.56/56.77

10 kW

100.8

177.9

1.16/42.21 2.15/78.24

Sound Attn. 84.6

126.6

1.06/38.57 1.7/61.86

Length of Pipe

Iron Pipe Size (IPS Inches)

½"

¾"

1"

1 ¼"

1 ½"

2"

15'

76

172

345

750

1,220

2,480

30'

52

120

241

535

850

1,780

45'

43

99

199

435

700

1,475

60'

38

86

173

380

610

1,290

75'

77

155

345

545

1,120

90'

70

141

310

490

1,000

105

65

131

285

450

920

120

120

270

420

860

150

109

242

380

780

180

100

225

350

720

210

92

205

320

660

240

190

300

620

270

178

285

580

300

170

270

545

450

140

226

450

600

119

192

390

Consumption in

Cubic Feet Per Hour