7

3. Refit the fitting and hose to the LP port and

the blanking plug to the natural gas port

(Figure 1.3).

4. Reverse the procedure to convert back to

natural gas.

NOTE:

The natural gas adjustment screw is preset during
installation and should not need any further
adjustment.

Figure 1.3 – LP Gas Setup

1.7 LOCATION AND MOUNTING

1.7.1 GENERATOR

Install the generator set, in its protective enclosure,

outdoors, where adequate cooling and ventilating air

always is available. Consider these factors:
• Install the unit where air inlet and outlet openings

will not become obstructed by leaves, grass, snow,

etc. If prevailing winds will cause blowing or drift-

ing, you may need to consider using a windbreak

to protect the unit.

• Install the generator on high ground where water

levels will not rise and endanger it.

• Allow sufficient room on all sides of the generator

for maintenance and servicing. A good rule is to

allow 3 feet of space on all sides.

• Where strong prevailing winds blow from one

direction, face the generator air inlet openings into

the prevailing winds.

• Install the generator as close as possible to the

transfer switch. This reduces the length of wiring

and conduit.

• Install the generator as close as possible to the fuel

supply, to reduce the length of piping. HOWEVER,

REMEMBER THAT LAWS OR CODES MAY REG-

ULATE THE DISTANCE.

1.7.1.1 6 kW, 8 kW and 10 kW Units (Non-SA)

These Guardian units are supplied with their own

mounting pads and DO NOT require a concrete pad.

Remove the packing material from the unit and unbolt

the two 4-inch by 4-inch wooden blocks from the

underside of the mounting base. Plug the holes with the

plugs provided. Prepare the installation site to accept

the mounting base. Provide adequate substrate to give

sufficient drainage, i.e., a 3-inch deep section of pea

gravel scattered under the mounting base.
See Figure 1.4 (Pages 8-9) for generator and transfer

switch major dimensions.

1.7.1.2 Sound Attenuated Units

Retain the generator compartment to a concrete slab

with 1/4-inch masonry type anchor bolts. Be sure the

bolts are long enough to retain the compartment. The

slab should be at least 3 inches thick and should

extend beyond the enclosure to a distance of at least

3 inches on all sides.
See Figure 1.5 (Page 10) for generator major

dimensions.

1.7.2 TRANSFER SWITCH

1.7.2.1 6 kW, 8 kW and 10 kW Units (Non-SA)

The transfer switch shipped with this generator is

enclosed in a NEMA 1 enclosure. This type of enclo-

sure is intended for indoor use only. Follow these

rules:
• Install the transfer switch indoors on a firm, stur-

dy supporting structure.

• To prevent switch distortion, level the switch

if necessary. This can be done by placing

washers between the switch enclosure and

mounting surface.

• Never install the switch where water or any corro-

sive substance might drip onto the enclosure.

• Protect the switch at all times against excessive

moisture, dust, dirt, lint, construction grit and

corrosive vapors.

1.7.2.2 Sound Attenuated Units

All sound attenuated models have a transfer switch

built into the enclosure and do not require a separate

switch attachment.