2 transfer back to utility, Power source, 5 protection systems – Generac 04077-01 User Manual

Page 22: 1 low oil pressure switch, 2 high temperature switch, 3 overcrank

Advertising
background image

20 Generac

®

Power Systems, Inc.

6. To crank and start the engine, set the

Auto/Off/Manual switch to MANUAL.

7. Let the engine stabilize and warm up for a few

minutes.

8. Set the generator’s main circuit breaker to its ON

(or closed) position. The standby power source

now powers the loads.

2.4.2 TRANSFER BACK TO UTILITY

POWER SOURCE

When utility power has been restored, you will want

to transfer back to that source and shut down the

generator. This can be accomplished as follows:
1. Set the generator’s main circuit breaker to its

OFF (or open) position.

2. Let the engine run for a minute or two at no-load

to stabilize the internal temperatures.

3. Set the generator’s Auto/Off/Manual switch to

its OFF (or open) position. The engine should

shut down.

4. Check that utility power supply to the transfer

switch is turned OFF.

Do not attempt to activate the transfer switch
manually until all power voltage supplies
to the switch have been positively turned off.
Failure to turn off all power voltage supplies
may result in extremely hazardous and possibly
fatal electrical shock.

5. Use the manual transfer handle inside the trans-

fer switch to move the main contacts back to their

“Utility” position, i.e., loads connected to the util-

ity power source (Figure 2.3, Page 19).

6. Turn ON the utility power supply to the transfer

switch using the means provided.

7. Set the system to automatic operation as

outlined in “Automatic Transfer Operation,”

Section 2.2 (Page 18).

2.5 PROTECTION

SYSTEMS

Unlike an automobile engine, the generator may have

to run for long periods of time with no operator pres-

ent to monitor engine conditions. For that reason, the

engine is equipped with the following systems that

protect it against potentially damaging conditions:
1. Low Oil Pressure Sensor
2. High Temperature Sensor
3. Overcrank
4. Overspeed

On sound attenuated models, there are LED read-

outs on the control panel to notify you that one of

these faults has occurred. There is also a “System

Set” LED that is lit when all of the following condi-

tions are true:
1. The Auto/Off/Manual switch is set to the AUTO

position.

2. The “Not In Auto” dip switch is set to the OFF

position on the control board.

3. No alarms are present.

2.5.1 LOW OIL PRESSURE SWITCH

This switch (Figure 2.4) has normally closed contacts

that are held open by engine oil pressure during

cranking and operating. Should oil pressure drop

below the 8 psi range, switch contacts close, and the

engine shuts down. The unit should not

be restarted until oil is added, and the

Auto/Off/Manual switch must be turned to OFF and

then back to AUTO.

2.5.2 HIGH TEMPERATURE SWITCH

This switch’s (Figure 2.4) contacts close if the tem-

perature should exceed approximately 140º C (284º

F), initiating an engine shutdown. Your generator will

automatically restart and the LED will reset once the

temperature has returned to a safe operating level.

Figure 2.4 – Low Oil Pressure and

High Temperature Switches

2.5.3 OVERCRANK

This feature prevents the generator from damaging itself

when it continually attempts to start and another prob-

lem, such as no fuel supply, prevents it from starting.

The unit will crank and rest for a preset time limit.

Then, it will stop cranking, and the LED will light indi-

cating an overcrank failure. The Auto/ Off/Manual switch

will need to be set to OFF and then back to AUTO to

reset the generator control board.

NOTE:

If the fault is not repaired, the overcrank feature
will continue to activate.