2.5.3.1 Approximate Crank Cycle Times

• 15 seconds ON

• 15 seconds OFF

• 7 seconds ON

• 7 seconds OFF

• Repeat for 45 seconds

Approximately 90 seconds total

2.5.4 OVERSPEED

This feature protects the generator from damage by

shutting it down if it happens to run faster than the pre-

set limit. This protection also prevents the generator

from supplying an output that could potentially damage

appliances connected to the generator circuit. The over-

speed feature will activate as follows:
1. If the generator runs at 72 Hertz for five seconds,

the generator will shut down.

2. If the generator reaches 75 Hertz, it will shut

down instantly.

2.6 ADDITIONAL

GENERATOR

FEATURES

2.6.1 6 KW, 8 KW AND 10 KW UNITS (NON-SA)

The standard 6 kW, 8 kW and 10 kW air-cooled

Guardians offer additional features that are not

factory preset:
1. Remote Start – This allows for remote starting of

the generator by means of the #183 (common)

and #178 (normally open) lines with the

Auto/Off/Manual switch set to AUTO. Closure of

the circuit starts the unit; opening of the circuit

stops the unit. See Figure 2.5.

NOTE:

This function will work ONLY with the unit in the
AUTO mode.

Figure 2.5 – Remote Start/Alarm Options

–Type 14 AWG wire is recommended.

–These options should be wired to the unit by a qualified electrician or

Generac/Guardian Authorized Dealer.

2. Remote/Common Alarm – This allows for an

alarm, light, horn, etc., to activate when any fault

has occurred. Lines #210 (common) and #211

(normally open) provide a “closure” on common

fault, which can be used for 120 volts, 10 amps

maximum. See Figure 2.5.

3. Remote Not Auto – The generator will not auto-

matically start during a utility failure.

2.6.2 SOUND ATTENUATED UNITS

Model 00844 of the sound attenuated air-cooled

Guardians offers additional features that are not factory

preset (see Figure 2.6):
1. Remote Start – This allows for remote starting of the

generator by means of the #183 and #178 lines with

the Auto/Off/Manual switch set to AUTO.

2. Engine Run Signal – The engine run signal is con-

trolled by the #14 line. The “volt free” engine run

signal relay closes when the #14 line is “hot.”

3. Automatic Transfer Switch (ATS) in Emergency –

For this to be active, a microswitch on the transfer

switch sends a signal along the #231 line to close

the “volt free” contact relay.

4. Shutdown Fault – This signal is controlled by the

main printed circuit board along the #229 line.

When a common fault occurs (low oil pressure,

high temperature, overspeed, overcrank), the

control board will send a signal along the #229

line to close the "volt free" contact relay.

Figure 2.6 – Remote Alarms

Section 2 — Operation

Guardian Air-cooled Generators

Generac

®

Power Systems, Inc. 21