5 checking automatic operation, 6 adjusting the load block – Generac 04077-01 User Manual

Page 25

Advertising
background image

Generac

®

Power Systems, Inc. 23

Do not attempt manual transfer switch
operation until all power voltage supplies to
the transfer switch have been positively turned
off. Failure to turn off all power voltage
supplies will result in extremely hazardous
and possibly fatal electrical shock.

4. Manually set the transfer switch to the STANDBY

position, i.e., load terminals connected to the

generator's E1/E2 terminals. The transfer switch

operating lever should be down.

5. Set the generator's Auto/Off/Manual switch to

MANUAL. The engine should crank and start

immediately.

6. Let the engine stabilize and warm up for a few

minutes.

7. Set the generator’s main circuit breaker to its ON

(or closed) position. Loads are now powered by

the standby generator.

8. Turn ON electrical loads. Apply an electrical load

equal to the full rated wattage/amperage capacity

of the installed generator.

9. Connect an accurate AC frequency meter across

terminal lugs E1 and E2. Voltage should be

greater than 230 volts; frequency should be

greater than 58 Hertz.

10. Let the generator run at full rated load for 20-30

minutes. Listen for unusual noises, vibration or

other indications of abnormal operation. Check

for oil leaks, evidence of overheating, etc.

11. When testing under load is complete, turn OFF

electrical loads.

12. Set the generator's main circuit breakers to their

OFF (or open) positions.

13. Let the engine run at no-load for a few minutes.
14. Set the Auto/Off/Manual switch to OFF. The

engine should shut down.

3.5 CHECKING

AUTOMATIC

OPERATION

To check the system for proper automatic operation,

proceed as follows:
1. Check that the Auto/Off/Manual switch is set

to OFF.

2. Manually set the transfer switch to the UTILITY

position, i.e., load terminals connected to the util-

ity power source side.

3. Turn ON the utility power supply to the transfer

switch, using the means provided (such as a util-

ity main line circuit breaker).

4. Set the Auto/Off/Manual switch to AUTO. The sys-

tem is now ready for automatic operation.

5. Turn OFF the utility power supply to the transfer

switch.

With the Auto/Off/Manual switch at AUTO, the engine

should crank and start when the utility source power

is turned OFF. After starting, the transfer switch

should connect load circuits to the standby side. Let

the system go through its entire automatic sequence

of operation.
With the generator running and loads powered by

generator AC output, turn ON the utility power sup-

ply to the transfer switch. The following should

occur:
• After about six seconds, the switch should transfer

loads back to the utility power source.

• About one minute after retransfer, the engine

should shut down.

3.6 ADJUSTING THE LOAD BLOCK

When the natural gas system is being used, the load

block is fitted with an adjustment screw that has

been calibrated to provide maximum power.

However, because of variations in the Btu content of

natural gas across the country, it may be necessary to

readjust the load block.
• Connect a frequency meter to the output of the

generator.

• Start the unit and apply full load according to the

following chart:

• Allow the unit to stabilize; then, turn the adjust-

ment screw slowly clockwise or counterclockwise

and watch the frequency.

• When the highest frequency is reached, turn the

adjustment screw counterclockwise 1/4 turn.

• The fuel system is now set.
• For LP gas operations, the hose and blanking plug

must be reconfigured as shown in Figure 1.3, Page

7. The unit is set to provide maximum power

using LP gas.

Do not make any unnecessary adjustments.
Factory settings are correct for most applica-
tions. However, when making adjustments, be
careful to avoid overspeeding the engine.

Section 3 — Post-installation Start-up Adjustments

Guardian Air-cooled Generators

Unit

120 Volts

240 Volts

6 kW

(Non-SA)

:

50 amps

25 amps

8 kW

(Non-SA)

:

66.7 amps

33.3 amps

10 kW

(Non-SA)

: 83.3 amps

41.6 amps

Sound Attn.:

66.7 amps

33.3 amps