4 functions rectifier / battery charger, Battery, Inverter – ETL EDP70 User Manual

Page 11: Electronic static switch, Switches

Advertising
background image

MI00/10056 rev. 8 — 05/2006-- page

11

Figure 2 – Block diagram – 50/80kVA

The uninterruptible power system consists of the following:

1 - RECTIFIER/INVERTER

S1 = Equipment ON/OFF switch

2 - BATTERY

S2 = Equipment Reserve switch

3 - BACKFEED PROTECTION

S3 = Equipment By-pass switch

4 - INVERTER STATIC SWITCH

S4 = Equipment OUTPUT switch

5 - RESERVE STATIC SWITCH

(INVERTER OUTPUT switch for 50/80kVA only)

S5 = RESERVE OUTPUT switch for 50/80kVA only

1.4

Functions

RECTIFIER / BATTERY CHARGER

The rectifier/battery charger transforms the alternating current of the mains supply to direct voltage to maintain the
battery in a fully charged state and also supply the inverter.

BATTERY

The battery is an energy reserve that is used by the inverter and the load whenever the mains supply fails.

INVERTER

The inverter changes the direct voltage from the rectifier or from the battery into a three phase sinusoidal alternating
voltage for the external supply.

ELECTRONIC STATIC SWITCH

The function of the electronic static switch is to select one of the two sources of alternating voltage and to supply it to the
external load. The two sources of voltage supplied to the static switch are the output of the inverter and the reserve
supply. In normal working conditions, the static switch supplies the load from the inverter.

SWITCHES

The switches permits maintenance and repair of the UPS, without interrupting the supply to the load.

3

Maintenance Bypass

IN THE ABSENCE OF A SEPARATE

RESERVE SUPPLY THE RESERVE IS

DERIVED FROM THE AC UTILITY

INPUT WITH THE JUMPER

CONNECTED AS INDICATED

AC Supply

240 Cells
(External)

Battery
Contactor

1

S1

480V

S2

Reserve
Supply

S3

2

4

480Y/277V

S4

5

208Y/120V

S5