ETL EDP70 User Manual

Page 26

Advertising
background image

page

26 --

MI00/10056 rev. 8 —05/2006

4.2

Installation

Check the rating label on the rear of the front panel of the EDP70 PLUS UPS to ensure the input/output voltages,
frequency and load are all within the rating of the UPS.

EDP70 PLUS is designed to operate in an office environment with an optimum temperature of 68°F [20 C].
A gap of at least 4 in [ 10cm. ] must be maintained at rear of the UPS to ensure adequate ventilation.
Nothing should be placed around the equipment which might restrict the airflow.
Ensure the interconnecting cables do not cause a hazard to the user.
A gap of at least 32 in [ 812 mm] must be maintained above the UPS to ensure adequate space for maintenance.
The appropriate lifting equipment must be used to move the EDP70 PLUS UPS.

Figure 16 –

UPS Ratings

UPS ratings

Description

U.M.

24

12kVA

24

18kVA

24

24kVA

36

24kVA

36

30kVA

36

36kVA

Output power

kVA

12

18

24

24

30

36

Nominal Load

kW

8

12

16

16

20

24

Maximum input power (with
unit @ nominal Load & battery
recharge)

kVA

15

21

28

28

35

42

Maximum dissipation (with
inverter @ nominal Load)

BTU/H

3750

5460

6800

7700

9500

11300

Number of battery cells

n

144

240

Battery voltage range

V

238-327

396-545

Battery
end-discharge current

A

37

55

74

53

67

80

UPS ratings

Description

U.M.

50

30kVA

50

40kVA

50

50kVA

80

50kVA

80

65kVA

80

80kVA

Output power

kVA

30

40

50

50

65

80

Nominal Load

kW

24

32

40

40

52

64

Maximum input power (with
unit @ nominal Load & battery
recharge)

kVA

43

57

71

71

91

112

Maximum dissipation (with
inverter @ nominal Load)

BTU/H

9300

11700

14300

14300

18600

22100

Number of battery cells

n

240

Battery voltage range

V

396-545

Battery
end-discharge current

A

67

88

110

105

140

173

Advertising