11.0 COMPUTER INTERFACE

11.1 AS400

The EDP70 PLUS UPS is fitted with a 9 pin female ‘D’ type socket for direct connection to a IBM AS/400 computer or
equivalent, see Figure 29. This facility can also be used with operating system software of other manufacturers. The
function of the pins on the socket are shown below:

Pin

Number

DESCRIPTION

FUNCTION NUMBER

8

EDP70 PLUS UPS ON

The UPS is supplying the load.

6

RESERVE TO LOAD

The reserve AC supply is supplying the load.

9

UTILITY SUPPLY FAIL

The AC utility supply to the UPS has failed.

7

BATTERY LOW

The battery capacity is at a minimum and the inverter
will shortly shut down and the load will be automatically
transferred to the reserve AC supply.

5

COMMON

All the above are connected to common when the
function is true.

Figure 29 EDP 70 Plus Computer Interface Pin Layout