ETL EDP70 User Manual

Page 2

Advertising
background image

page

2 --

MI00/10056 rev. 8 —05/2006

IMPORTANT SAFETY INSTRUCTIONS
READ BEFORE INSTALLING


1) SAVE THESE INSTRUCTIONS

This manual contains important instructions for the EDP70 PLUS which should be followed during
installation and maintenance of the UPS and associated batteries.

2)

The installation must be inspected by trained technicians.

The instructions must be followed.

3)

When external batteries are provided by the Customer and not Chloride, reference must be made to

the installation instructions provided by the battery supplier.

WARNINGS

1)

The AC and DC supplies to the EDP70 PLUS UPS and the AC output from the UPS MUST be fed

through suitably rated circuit breakers or fuses and isolating switches suitable for branch circuit operation.

2)

Any external battery cabinet connected to the UPS MUST be provided with an over-current protection

device per UL1778 Par. No. 28.4

3)

To reduce the risk of fire or electric shock, the equipment must be installed indoors, in a humidity

and temperature controlled environment which is free from conductive contaminants.

SAFETY

1)

DO NOT REMOVE COVERS DURING NORMAL OPERATION. The panels will be removed during

installation, however this should only be undertaken by qualified technicians. It should be ensured
that the UPS is switched off and that all power sources are disconnected (A.C. mains and Battery)
before either the rear or side panels are removed.

2)

FOREIGN OBJECTS MUST NOT BE INTRODUCED INTO THE VENTILLATION GRILLES.

HAZARDOUS VOLTAGES are present within the EDP70 PLUS even when it is switched off.

3)

Fuses must ONLY be replaced with the same type and rating.

4)

The EDP70 PLUS contains a battery which can be DANGEROUS if interfered with. Contact the

supplier for replacement.

5)

The UPS and/or its components must be disposed of as notifiable waste in accordance with local

pollution control (special waste) regulations.


Advertising