10.6 Power History

The power history is only available when the inverter is blocked; it provides a visual display of the status of the alarms
and measurements over a period of 10 seconds before and 1 second after the inverter stops in steps of 0.1 s. The power
history is lost when the inverter is restarted.

Figure 28

provides a graphic representation of how to access the Power History.



Figure 28: Power History Structure

LOAD

ALARMS

POWER HISTORY

DOWN TO ACCESS

BATTERY TEST

SELECT

POWER HISTORY MATRIX

Time

(seconds)

-10

Alarms

Measurements

Initial

position

Inverter

Shutdown

Typical Power History Display

Measurement

Alarm

RECTIFIER +0.3 SEC

VDC = 327V IB = 5A

-5.3 SEC ON

OVER TEMPERATURE

POWER HISTORY

UP TO EXIT

+1

0