MI00/10056 rev. 8 — 05/2006-- page

33

5.2

24 – 12/18/24kVA

Ensure the AC supplies and load are switched OFF. Check that all the EDP70 PLUS UPS Switches (behind the front
panel) are switched OFF, see Figure 18 .

The AC supply cables must be suitable for carrying the maximum supply demand. The voltage drop in the cable
should be minimized to ensure the AC supply voltage at the EDP70 PLUS UPS terminals is within +/- 10% of nominal.

The EDP70 PLUS UPS should be connected to the main/reserve supplies and output load via a wall mounted junction
box.

Installation and connection should only be carried out by qualified electrical personnel.

Figure 18 - 24 – 12/18/24kVA: Switches and Breakers

Battery Compartment

S2 = Equipment Reserve Switch

S1 = Equipment ON/OFF Breaker

S3 = Equipment By-pass Switch

S4 = Equipment OUTPUT Breaker