Figure 3 – Normal operation

During normal operation the load is supplied by the mains through the rectifier and inverter. The rectifier also supplies
the current for recharging and maintaining the battery in a fully charged state.

Figure 4 – Utility Supply failure

When the utility supply voltage is absent or outside the allowed tolerances, the battery supplies the inverter. This will be
indicated on the UPS front panel display and the Remote Alarm Unit (if fitted). The standby time available depends both
on the capacity of the battery and on the size of load. It is possible to extend autonomy by reducing the output power by
disconnecting non-important loads. In all cases, the alphanumerical display shows the residual autonomy.