DIAGNOSTIC STATUS CODES

SX TRANSISTOR CONTROL

Page 21

January 2000

TRACTION

STATUS CODE

DESCRIPTION OF STATUS

CAUSE OF STATUS INDICATION

-02

Forward directional switch is closed on
initial power up.

This status code will be displayed when P4 is greater
than 60% of battery voltage at initial key switch on.

MEMORY RECALL

NO

CORRECTIVE ACTIONS

TROUBLE-SHOOTING DIAGRAM

Circuits valid

for

Traction

Controller

SYMPTOM
Control will not operate because of Static Return
to Off (SRO) lock out.

POSSIBLE CAUSE
Forward directional switch is closed on initial
start up (i.e. closure of battery, key switch or
seat switch).

= Return directional switch lever to neutral and

then return lever to forward position.


Forward directional switch is welded closed or
mis-adjusted to be held closed.

= Replace or adjust directional switch to insure

that it opens when the directional switch is
returned to neutral.


Short circuit between P3 and P4.

= Disconnect the wire from P4 and check for a

short circuit between P3 and the wire that was
connected to P4.


Defective control.

= Replace the controller unit.

KEY

SWITCH

P1

P2

P3

P17

P5

REVERSE SW

.

F

O

RWARD SW.

P4

SEAT

SW

IT

CH

P6

L

ST

ART

SW

.

TRACTION

STATUS CODE

DESCRIPTION OF STATUS

CAUSE OF STATUS INDICATION

-03

Reverse directional switch is closed on
initial power up.

This status code will be displayed when P5 is greater
than 60% of battery voltage at initial key switch on.

MEMORY RECALL

NO

CORRECTIVE ACTIONS

TROUBLE-SHOOTING DIAGRAM

Circuits valid

for

Traction

Controller

SYMPTOM
Control will not operate because of Static Return
to Off (SRO) lock out.

POSSIBLE CAUSE
Reverse directional switch is closed on initial
start up (i.e. closure of battery, key switch or
seat/deadman switch).

= Return directional switch lever to neutral and

then return lever to reverse position.


Reverse directional switch is welded closed or
mis-adjusted to be held closed.

= Replace or adjust directional switch to insure

that it opens when the directional switch is
returned to neutral.


Short circuit between P3 and P5.

= Disconnect the wire from P5 and check for a

short circuit between P3 and the wire that was
connected to P5.


Defective control. Replace the controller unit.

KEY

SWITCH

P1

P2

P3

P17

P5

REVERSE SW

.

F

O

RWARD SW.

P4

SEAT

SW

IT

CH

P6

L

ST

ART

SW

.