When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are
memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the moment power
has restored after power failure.Then, the unit will restart automatically. However if the unit is operated in “I FEEL CON-
TROL.” mode before power failure, the operation is not memorized. In “I FEEL CONTROL.” mode, the operation is decided
by the initial room temperature.

How to set “AUTO RESTART FUNCTION”

1

Turn off the main power for the unit.

2

Removed the electronic control P.C. board and the display P.C.board. (See page 60 and 62.)

3

Cut the RESISTOR JR07 (MSH-07/09/12) or JR06(MSH-18/24) on the indoor electronic control P.C.board.

C11

52C

CN201

CN1

12

CN121

SW

CN1

1

1

IC101

CN21

1

CN151

JR07

JR06

CN102

CN151

CN1

12

CN1

1

1

CN121

CN101

BZ

SW

52C

IC101

RA102

IC141

CN21

1

C1

1

CN201

Operation

1

If the main power (220/240V AC) has been cut, the operation settings remain.

2

After the power is restored, the unit restarts automatically according to the memory.(However, it takes at least 3 minutes

for the compressor to start running.)

Note:

The operation settings are memorized when 10 seconds have passed after the remote controller was operated.

If main power is cut while AUTO START/STOP timer is active ,the timer setting is cancelled when auto restart function

works.

If the unit has been off with the remote controller before power failure, the auto restart function does not works as the

power button of the remote controller is off.

To prevent breaker off due to the rush of startting current, systematize other home appliance not to turn on at the same

time.

When more than one air conditioners are connected under the same power system,compressor starting current as large

as that for all the compressors used flows at a time as soon as the units restart automatically.

Therefore, the specific counter-measures are required to prevent main voltage drop or the rush of starting current after

power failure by providing the system to allow the units to start in regular succession.

MSH-07/09/12

MSH-18/24

5. AUTO RESTART FUNCTION

MSH-07NV -

MSH-09NV -

MSH-12NV -

MSH-24NV -

MSH-18NV -

E3

E2

E2

E2

E2

OB207t-2qxp 25/9/97 8:55 PM Page 46

Advertising
This manual is related to the following products: