MITSUBISHI ELECTRIC MSH-07NV User Manual

Page 49

Advertising
background image

49

10-2-1 troubleshooting check table

Before taking measures, make sure that the symptom reappears, for accurate troubleshooting.

Self check table

NO.

1

2

3

4

Abnormal

point

Mis-wiring

Serial sig-
nal

Indoor coil
thermistor

Room
tempera-
ture ther-
mistor

Indoor fan
motor

Outdoor
thermistor

Indication

0.5-second ON

0.5-second OFF

1-time flash

2.5-second OFF

2-time flash

2.5-second OFF

3-time flash

2.5-second OFF

6-time flash

2.5-second OFF

Symptom

Outdoor unit
does not run.

Outdoor unit
does not run.

Indoor fan
repeats 12 sec-
onds ON and 3
minutes OFF.
When the indoor
fan breaks, the
fan keeps stop-
ping.

Outdoor unit
does not run

Detect method

When serial signal stops for 4
to 5 seconds after 1st on of
52C relay by POWER turning
on.

When serial signal from out-
door unit stops for 4 to 5 sec-
onds.

Detect Indoor coil/room tem-
perature thermistor short or
open circuit every 2 seconds
during operation.

When rotational frequency
feedback signal is not emit
during 12-second indoor fan
operation.

When the outdoor thermistor
shorts or opens after the com-
pressor start-up.

Check point

Check wiring (visual check and conductiv-

ity check).

Check indoor electronic control

P.C.board.

Check outdoor DEICER P.C. board.

Check electrical parts.

Check thermistor calibration.

Reconnect connector.

Check indoor electronic control P.C.board.

Disconnect connector CN211 and then

check connector CN121 - to make
sure rotational frequency feedback signal
of 1.5V or over exists.

Check indoor electronic control P.C.

board.

Check indoor fan motor.

Reconnect conector.

Shortage of refrigerent.

Check outdoor DEICER P.C. board.

2

3

5

Outdoor
power
system

5-time flash

2.5-second OFF

Outdoor unit
does not run

When the compressor opera-
tion is continuosly three times
interruped by overcurrent pro-
tection within 1 minute after
start-up , it stops operation.

Check the inverter output.

Check the compressor.

6

Outdoor
control
P.C. board

7-time flash

2.5-second OFF

Outdoor unit
does not run

The outdoor unit stops opera-
tion when it cannot properly
read data in the nonvolatile
memory of the outdoor control
P.C.board.

Check the outdoor control P.C.board.

7

Outdoor
control
P.C. board

10-time flash

2.5-second OFF

Outdoor unit
does not run

When the indoor unit detects
drain abnormality and the
indoor coil temperature is too
low.

Check the drain punp.

Check the drain sensor.

Check LEV.

8

Outdoor
control
P.C. board

light 2.5-second OFF
flash

Outdoor unit
runs but the
indoor unit does
not run.

When the operation mode of
each rooms is setted
COOL(includes DRY) and
HEAT at same time, it take
precedence the operation
mode runs first.

Adjust the operation mode.

The indication is shown only when the indoor unit connects with the outdoor unit MXZ-32NV-

.

E1

OB207t-2qxp 25/9/97 8:55 PM Page 49

Advertising
This manual is related to the following products: