Millennium Enterprises Net Safety MLP-A/AR User Manual

Page 11

Advertising
background image

Net Safety Monitoring Inc

MLP-A/AR/AD-ST1400-25

6

Figure 5: Wiring—Controller and Sensor

Note:

If the 4-20 mA signal is not used, connect a jumper between the 4-20
terminal and the COM terminal on the Terminal Board.

S

ENSOR AND

C

ONTROLLER

WARNING:
Power to the unit must be OFF before wiring.

Note:

The Sensor may be factory installed to the Controller. If so, you need
only connect the Power Terminals.

1. Remove the Controller’s Housing Cover.
2. Connect the Sensor to the Sensor Terminals (if necessary) and the Output

Terminals to the output signal wires.

Note:

For Sensor Separation instructions, see Figure 6, "Wiring—Sensor
Separation", on page 7.

3. Replace the Controller’s Housing Cover.
4. Turn Controller On.
5. Ensure display reads

Start Delay

, Status LED is Red Slow Flash and

current output displays 3.0 mA. This is the start-up delay sequence which
will last approximately 90 seconds.

RS-485 Communication

Connect devices in a chain via the Modbus terminals. The last device in the
chain requires end of line termination (refer to "MODBUS Termination" on
page 9).

RST

+24V

COM

4-20

ISO

Red+

Blk

Shld

Red
Blk
-
-
Shld

Terminal Board

Sensor
Wires

Terminals

Modbus RTU

to PLC

A

B

COM

-

Terminals

Power

RST
+24V
COM
4-20
ISO

Terminals

Sensor

Sensor Board

Table 1: Controller/Sensor Connections

Sensor Board Terminals

Terminal Board Power

Sensor
Wire

Controller
(Sensor Board)

Controller
(Terminal Board)

Power
Connections

Red

= Red (+24 V)

RST

= Remote Reset

Black

= Blk (Sig)

+24V

= Power (+)

-

COM

= Power (-)

-

4-20

= Current Loop

Output

Shield

= Shld

ISO

= +24 V isolated

4-20 power