Step 3 — w – Millennium Enterprises Net Safety MLP-A/AR User Manual

Page 9

Advertising
background image

Net Safety Monitoring Inc

MLP-A/AR/AD-ST1400-25

4

Mount

The Controller is usually mounted near eye-level and be easily accessible for
calibration and maintenance purposes. The Sensor should be placed where O2
may build up or where other gases are likely to build up and displace O2.

Ensure all devices are securely mounted, taking into consideration all
requirements.

STEP 3 — W

IRE

F

IELD

I

NSTALLATION

WARNING: Wiring codes and regulations may vary. Compliance with
regulations is the responsibility of the installer. Wiring must comply with
applicable regulations relating to the installation of electrical equipment in a
hazardous area. If in doubt, consult a qualified official before wiring the system.

• If the 4-20 mA signal is not used, connect a jumper between the 4-20 terminal

and the Common terminal.

• The use of shielded cable is highly recommended for signal, input, output and

power wires to protect against interference caused by extraneous electrical or
electromagnetic 'noise'.

• In applications where the wiring cable is installed in conduit, the conduit

must not be used for wiring to other electrical equipment.

• The maximum distance between the Sensor and Controller is limited by the

resistance of the connecting wiring, which is a function of the gauge of the
wire being used (refer to " Resistance Table in OHMS" on page 21).

• When developing a RS-485 chain of devices, the last device in the chain

requires end of line termination.

• RS-485 connection 2-wire, multipoint serial line.

S

EAL

• Water-proof and explosion-proof conduit seals are recommended to prevent

water accumulation within the enclosure.

• Seals should be located as close to the device as possible and not more than

18 inches (46 cm) away.

• Explosion-proof installations may require an additional seal where conduit

enters a non-hazardous area. Ensure conformity with local wiring codes.

• When pouring a seal, use a fibre dam to assure proper formation of the seal.

Seals should never be poured at temperatures below freezing.

• The jacket and shielding of the cable should be stripped back to permit the

seal to form around the individual wires. This will prevent air, gas and water
leakage through the inside of the shield and into the enclosure.

• It is recommended that explosion-proof drains and conduit breathers be used.

In some applications, alternate changes in temperature and barometric
pressure can cause 'breathing' which allows moist air to enter and circulate
inside the conduit. Joints in the conduit system are seldom tight enough to
prevent this 'breathing'.

Note:

Seals are not required for all Class 1 Division 2 locations in Canada.
However, to fully avoid any exposure, the use of seals are still
recommended, especially for installations that use high-pressure or
steam cleaning devices in proximity to the controller and/or sensor.

Connecting Wires

1. Use a small screw driver to gently press down and hold the spring connector

open.

2. Insert appropriate wire into open connector hole.
3. Release screw driver to secure wire.

Use the Face Rotation Option to mount the Millennium
Controller at a different orientation (refer to "Face
Rotation Option" on page 19 for detailed instructions).