Millennium Enterprises Net Safety MLP-A/AR User Manual

Page 16

Advertising
background image

Net Safety Monitoring Inc

MLP-A/AR/AD-ST1400-25

11

RTU Registers

Register 40001 = % output (read only)

Register 40002 = RTU Status (read only)

Register 40101 = Reset latched relays (write)

Calibration Button

The Calibration Button provides access to the Millennium’s Main Menu, which
in turn allows calibration and options to be reviewed and set. Refer to Figure 12,
"Controller Functionality", on page 10 for more information.

Press and hold the Calibration Button to Calibrate and access Main Menu.

Briefly press to make a selection (select

YES?

).

WARNING:
Opening the Controller’s Housing should be avoided when the
presence of gas is possible (when in a hazardous environment). Do
not power up the system, with the Housing removed, unless the area
has been de-classified.

Table 2: Status LEDs, Display Messages and Current Loop

Status LED

State

Current O/P

RED or GREEN

Display

Options
Review/Settings

3.0 mA

n/a

n/a

Standard level of
Oxygen present

17.4 mA

Blip/
blink

20.9 %O2

Start-up delay (90 sec) 3.0 mA

Slow
flash

Start Delay

Access Main Menu

3.0 mA

n/a

Switch On

10-0

Memory Error (contact
factory)

2.5 mA

Slow
flash

Memory Error

Black or Red Sensor
lead open

2.5 mA

Slow
flash

Sensor Fault

Auto zero set

3.0 mA

Solid

Apply Clean

Air

Apply calibration gas

3.3 mA

Fast
flash

Apply 20.9%

O2

Span is set, remove
gas

3.6 mA

Solid

Remove gas

Low alarm set point

-

Flash

XX Low Alarm

High alarm set point

-

Flash

XX High Alarm

Non-standard levels of
Oxygen present

>17.4 mA or
<17.4 mA

Blip/
blink

% O2

shown left

side display

Calibration procedure
failed/Sensor failed

3.0 / 3.3 mA

Flash

Flash

Fail Cal

Over 25% Range

20 mA

Solid

<25%O2

Table 3: RTU Status Register (40002) Read Only (Binary)

RTUstat_fault

0x0001

(fault sensor...)

RTUstat_low_alarm

0x0002

low alarm tripped

RTUstat_high_alarm

0x0004

high alarm tripped

RTUstat_low_alarm_latched

0x0008

low alarm latched

RTUstat_high_alarm_latched

0x0010

high alarm latched

RTUstat_powerUp

0x0080

power up delay

RTUstat_cal_cycle

0x0100

calibration cycle in progress

RTUstat_zeroing

0x0200

RTUstat_apply_span_gas

0x0400

RTUstat_calibrating

0x0800

RTUstat_remove_gas

0x1000

RTUstat_cal_complete

0x2000

RTUstat_mem_error

0x4000

memory error